Page 323 - Catalogue Elec
P. 323
TeSys
TeSys GB Thermal-magnetic circuit breakers for auxiliary circuits
Introduction
Introduction
PB110899_20.eps PB110901_20.eps GB2 thermal-magnetic circuit breakers protect and isolate the control circuits of
industrial equipment with contactor coils, transformers.…
They protect and isolate single-phase auxiliary circuits such as solenoid valves,
electro-brakes, battery chargers, supplied from the control circuit voltage.
GB2CB, GB2CD, GB2DB
12 ratings are available, from 0.5 to 20 A, in single-pole (GB2CB), single-pole +
neutral (GB2CD) and 2-pole (GB2DB) versions.
They have a magnetic tripping threshold set at between 12 and 16 In to withstand the
current peaks generated by many industrial components.
GB2CS
2 ratings are available, 0.5 and 1 A, in single-pole version.
GB2CB GB2CD The magnetic tripping threshold is set between 5 and 7 In.
Functions, installation
PB110902_20.eps PB110900_20.eps Clip-on fixing onto all types of 35 mm 5 rails, on 4 rails and on Telequick
mounting plates.
Upstream and downstream marking by means of AB1 clip-in markers.
Clear indication of “I” and “O” positions on the operator.
Tamper-proof device which requires no special maintenance (fixed magnetic and
thermal tripping thresholds).
Selection for the protection of circuits supplied by transformers
Single-phase transformers.
Magnetising peak: 20 In.
Operation of magnetic trips: 13 In.
Power Primary (1) 380/415 V Secondary 48 V 110 V 220 V
24 V
VA
220/240 V
Circuit breakers GB2DB GB2CS 40 GB2DB05 GB2DB05 GB2CD07 GB2CD06 GB2CD05 GB2CD05
63
GB2CD07
GB2CD06
GB2DB05
GB2CD05
GB2CD08
GB2DB05
100 GB2DB06 GB2DB05 GB2CD10 GB2CD07 GB2CD06 GB2CD05
160 GB2DB07 GB2DB06 GB2CD14 GB2CD09 GB2CD07 GB2CD06
250 GB2DB07 GB2DB06 GB2CD16 GB2CD12 GB2CD08 GB2CD07
400 GB2DB08 GB2DB07 GB2CD22 GB2CD14 GB2CD09 GB2CD07
630 GB2DB10 GB2DB08 – GB2CD21 GB2CD12 GB2CD08
1000 GB2DB14 GB2DB09 – – GB2CD16 GB2CD10
1600 GB2DB20 GB2DB14 – – – GB2CD14
2000 GB2DB21 GB2DB14 – – GB2CD22 GB2CD16
2500 GB2DB22 GB2DB20 – – – GB2CD20
3000 GB2DB22 GB2DB20 – – – GB2CD21
4000 – GB2DB21 – – – GB2CD22
5000 – GB2DB22 – – – –
(1) If the breaking capacity of the GB2 is insufficient, use a GV2RT with 2 poles connected in
series.